The level recorder performs the following functions:
- Registers and records “liquid/gas” states on one or two controlled levels (controlled levels are determined by the placement of the sensors on the outer surface of the tank)
- Automatic or manual management of the actuator (latch or valve)
- Automatic calculation of the number of discharge / filling cycles
- Display on the graphic display of the recorder the level of liquid with respect to the controlled levels, the state of the actuator and the number of cycles
- Reception and transmission of telemetric data to an external telemetry system
- Internal diagnostics of the performance of the recorder and its tuning
- Archiving of operational parameters
№ | Name | Parameter |
1 | Number of control levels | 1-21 |
2 | Distance between the upper and lower levels, mm | 50-20002 |
3 | Accuracy of the liquid level detection, mm | ±10 |
4 | Wall thickness of the controlled tank, mm | 3-70 |
5 | Outer diameter of the controlled tank, no less than, mm | 100 |
6 | Controlled tank’s wall temperature, °С | from -50 to +60 |
7 | Range of Display of level changes, mm | from 100 to 4000 3 |
8 | Power source: | |
8.1 | CDU: | |
-Kind of current | AC | |
- Voltage, В | V220 +22/-44 | |
- Power consumption, no more, W | 20 | |
Maximum input voltage, Um, В | 250 | |
No-load voltage, Uo, V | 24 | |
Capacity limit, Co, ufd | 0,114 | |
Inductivity limit, Lo, mH | 1,54 | |
8.2 | SPU with SUs: | |
Number of channels | 2 | |
Input voltage limit, Ui, V | 13-18 | |
Maximum input current, Ii, mA | 40 | |
Maximum input capacity, Ci, ufd | 0,11 | |
Maximum input inductivity, Li, mH | 1,5 | |
9 | Relay output characteristics: | |
-number of outputs, pcs | 2 | |
-commutated voltage, no more than, V | 250 | |
-commutated current, no more than, A | 1 | |
10 | Protection against external influences, SPU together with SUs | DB IP54 |
11 | Protection against external influences, CDU | IP40 |
12 | Distances between the SPU and the SUs, m | 1;21 |
13 | Length of the link between the SPU and the CDU, no more than, m | 10004 |
14 | Mean time to failure, no less than, h | 30000 |
15 | Service life period, no less than, yrs | 15 |
16 | Operation mode | continuous |
1 At the Customer’s request
2 At the Customer’s request, Position 2 of Table 1 can be implemented with the max distance of up to 10 m.
3 At the Customer’s request, and only for the customized option of the secondary CDU unit.
4 The Customer ensures the use of cables with the parameters that do not exceed those specified in this data sheet.
Dimensions and weight
Part names | Length | Width | Height | Weight, kg | Note |
CDU | 140 | 140 | 54 | 1.25 | |
SPU | 200 | 300 | 160 | 5.7 | |
SUs | 36 | 36 | 31 | 0.4 | 4 products for two controlled levels |
Gross Weight - 10 kg